Physics Part 67
You’re reading novel Physics Part 67 online at LightNovelFree.com. Please use the follow button to get notification about the latest chapter next time when you visit LightNovelFree.com. Use F11 button to read novel in full-screen(PC only). Drop by anytime you want to read free – fast – latest novel. It’s great if you could leave a comment, share your opinion about the new chapters, new novel with others on the internet. We’ll do our best to bring you the finest, latest novel everyday. Enjoy!
The magnetic field of an alternating current not only rapidly reverses itself, but also continually _changes in intensity_. At the instant when the current reverses, the force of the magnetic field is zero since the current at that instant is zero. As the current begins flowing and increases to its maximum intensity, the magnetic field appears and increases in intensity; and as the current decreases to zero, the magnetic field changes in a similar manner. The field as it grows in strength extends farther and farther from the wire, as it decreases in strength it contracts or draws closer to the wire. Thus the magnetic field may be said to expand and contract. We may picture the lines of force as continually moving. In a typical a.-c. circuit, the complete series of changes takes place in a small fraction of a second, and is repeated many times over in a second. Contrast this with the magnetic field of a constant direct current. Here the magnetic field has the same direction as long as the current flows and does not change in strength.
This comparison is important because most of the differences between direct and alternating currents depend on differences in the action of their magnetic fields.
[Ill.u.s.tration: FIG. 430.--Arrangement of compa.s.ses about a wire carrying an alternating current.]
=430. Transformers.=--The transformer has been described in Arts.
309-310. The principle of the transformer may be ill.u.s.trated by the following experiment:
A coil having several hundred turns of No. 18 d.c.c. copper wire is placed over one arm of a "U" shaped iron core (see Fig. 431) and then connected to a 110 volt a.-c. lighting circuit. Another coil (_S_) having about 50 turns of No. 22 d.c.c. copper wire is connected to an electric bell or buzzer, or a low voltage electric light bulb. When the small coil is held over the other arm of the "U" shaped iron core, the bell rings or the bulb glows. It is evident that the electromotive force developed in the small coil (_S_) is due to the alternating magnetic field surging back and forth through the iron core. In Fig. 431 the core is "open" since the magnetic field must pa.s.s through the air from one end of the core to the other. A typical transformer has a _closed core_ to provide a _closed magnetic circuit_. To secure this, take a suitable bar of iron and lay across the end of the "U" shaped core, and notice any change in the induced current produced in the small coil, due to increased movement of magnetism through the closed iron core.
[Ill.u.s.tration: FIG. 431.--Diagram of a transformer.]
This experiment ill.u.s.trates the construction and action of a transformer. In a commercial transformer, the two windings are on a closed magnetic circuit. (See Figs. 304 and 305, p. 346.) To keep the coils insulated, the transformer is placed in an iron "housing" and covered with oil. These "housings," or transformer cases are generally attached to poles near buildings in which alternating current is used.
=431. Voltage Relation in a Transformer.=--In the experiment described above, a bell was rung by an induced current produced in the secondary coil. The induced e.m.f. was less than the voltage of the primary coil partly because there was some magnetic leakage, but mainly because there were fewer turns of wire on the secondary. In a commercial transformer the magnetic leakage is practically zero. In such a case, the ratio of the number of turns on the primary coil to the number on the secondary equals the ratio of the e.m.f. induced in the primary to the e.m.f. induced in the secondary. Suppose, for example, we wish to make a bell ringing transformer to use on a 110 volt lighting circuit, 10 volts being required for the bell; the secondary will then need one-eleventh of the number of turns of the primary. So that if 550 turns are on the primary, then 50 turns will be needed for the secondary. This will be a "step-down" transformer. On the other hand, suppose we wish to "step-up" the voltage as is done in a certain power station where the voltage of the generators is 6000 volts, the voltage being stepped up to 44,000 by means of large transformers. This means that the secondary coils have approximately 7-1/3 times as many turns as the primary.
=432. Power Loss in a Transformer.=--When the voltage is "stepped up" in a transformer, do we gain power? To answer this question we must remember that electric power does not depend on voltage alone but on the _product_ of e.m.f. and current intensity. (See Art. 291.) By tests with a.-c. voltmeters and ammeters, we find that when the secondary e.m.f. is _greater_ than the primary e.m.f., the secondary current intensity is _less_ than that in the primary. It is also found that the _power_ developed is less than the power received by the transformer, _i.e._, the "output" is less than the "input" as we would expect from the law of machines. The power loss is mainly due to the work required to reverse the magnetism, that is, to continually reverse the position of the iron molecules. (See Art. 205.) The energy lost in this manner is known as "core loss" since it occurs in the iron core. The lost energy appears as heat. So much heat is developed in large transformers that special means of cooling are provided. In order to make the heat developed as small as possible, the cores are "laminated" (see Fig. 305, p. 346), that is, built up of thin sheets of iron, because if the iron cores were solid, the changing magnetic fields would induce electric currents in the iron cores, which would produce an excessive amount of heat with a correspondingly large power loss.
[Ill.u.s.tration: FIG. 432.--Diagram of "bell-ringing" transformer.]
=433. Choke Coils and Inductance.=--If we refer to Fig. 432 we see that the primary winding of the bell ringing transformer is connected across the line. This winding forms a closed circuit whether the bell is ringing or not. The resistance of this winding is small. Let us a.s.sume it to be one ohm. With a one ohm resistance connected across a 110 volt line we might expect a current of 110 amperes. This is certainly what we should get if we were to connect a one ohm resistance across a line having 110 volts direct. The primary would form a short circuit if the current were direct. But the fact is that practically no current flows through the primary winding when the bell is not ringing. Herein lies one of the important differences between alternating and direct currents. With an alternating current the primary winding of our transformer acts as a _choke coil_ and "chokes" down the current almost to zero. Let us see how this is done.
[Ill.u.s.tration: FIG. 433.--A circuit containing a choke coil.]
Let Fig. 433 represent a choke coil. Since alternating current is used, the magnetic field is continually changing. Each turn of wire has its own magnetic field. The lines of force of turn number 1 expand and contract and as they do so they move across turns 2, 3 and so on. In like manner the lines of force from each turn of wire move across the other turns. In other words the coil is cutting its own lines of force.
Now whenever an electric conductor cuts magnetic lines of force an electromotive force is induced in the conductor. There is then an e.m.f.
induced in the coil by its own magnetic field. This induced e.m.f. on the whole opposes the applied e.m.f.; in the primary of our bell ringing transformer the induced e.m.f. opposes the e.m.f. of the line to such an extent as to reduce the current almost to zero. _Inductance_ is the action of an alternating current in inducing an opposing e.m.f. in the coil in which the current is flowing. Since this opposing e.m.f. is induced in the coil by its own magnetic field this action is also called _self-induction_. In a transformer the action of the field of the primary upon the secondary is _mutual induction_; while the action of the field of the primary in choking the current in the primary itself is self-induction or inductance. A coil having a single winding and used to introduce inductance in a circuit is called a _choke coil_. A choke coil inserted in a lamp circuit in series with the lamps dims the lamps because it reduces the intensity of the current.
[Ill.u.s.tration: FIG. 434.--Diagram showing graphically an alternating current with a "lag" of 30 behind its electromotive force.]
Self-induction causes the current to _lag_, that is, the current does not quite reach its maximum at the instant the voltage reaches its maximum. Fig. 434 shows graphically an e.m.f. and a lagging current. In this figure the maximum current is shown following the maximum voltage at an interval of 30 degrees. In other words the armature in a two-pole field must turn 30 degrees from the position of maximum voltage before the current in the coil, where the self-induction occurs, reaches its maximum.
=434. Reactance and Impedance.=--A choke coil has resistance as well as inductance. Its resistance can be found by the voltmeter-ammeter method, using a direct current. (See Art. 278.) Let us take for example the primary winding of a bell ringing transformer. Using a direct current and testing the coil with a voltmeter and ammeter we find its resistance to be, let us say, one ohm. If we connect the same coil across a 110 volt a.-c. line we find the current to be very small, say 0.05 ampere.
The coil now has resistance and _reactance_. Reactance is the effect of self-induction in hindering the flow of current. It is measured in ohms.
The combined effect of resistance and reactance is called _impedance_.
In the example above, the coil has 110 (volts)/0.05 (ampere) = 2200 ohms of impedance. In applying Ohm's law to an alternating current circuit, impedance must be subst.i.tuted for resistance. Ohm's law as applied to an a-c. circuit should be stated: "Current intensity equals e.m.f. divided by impedance", or _I_ = _E_/_Z_. (_Z_ = impedance.)
[Ill.u.s.tration: FIG. 435.--The relation between resistance, reactance and impedance.]
Impedance, however, does not equal the _sum_ of resistance and reactance. The relation between these three quant.i.ties is similar to that between the three sides of a right triangle, in which the impedance represents the hypotenuse, and the resistance and reactance the other two sides. See Fig. 435 which indicates that Resistance + Reactance = Impedance, or (_R_ + _X_ = _Z_). (_X_ = reactance.) To ill.u.s.trate this relation; suppose the primary of a transformer has 10 ohms impedance and 8 ohms resistance, then the reactance equals 10 - 8 = 6, or the reactance is 6 ohms.
Exercises
1. Find the reactance of a choke coil having a resistance of 10 ohms, when its impedance is 50 ohms. How great a current flows through this coil if the terminal voltage is 110 volts?
2. When the bell is ringing, the primary of a bell ringing transformer has an appreciable current. Suppose this current is 0.2 ampere. What is the impedance if the voltage of the line is 115 volts? What is the reactance if the resistance is 1 ohm?
3. The primary of a large transformer has a terminal voltage of 6000 volts and a current of 600 amperes. What is the impedance? If the resistance is 6 ohms, what is the reactance?
[Ill.u.s.tration: FIG. 436.--A telephone set showing a condenser used in the circuit of the "ringer."]
=435.--The electric condenser= (see Art. 231) is a very useful device in a.-c. circuits; _e.g._, in telephone sets used in cities, a condenser is used in the ringing circuit, as shown in Fig. 436. Alternating current is required to ring such a bell and a condenser permits an a.-c. current to act through it, although it entirely prevents the flow of a direct current. This peculiar action will now be explained.
=436. The action of a condenser= in an alternating current circuit may be ill.u.s.trated by the following experiment. Connect twelve, 1 m.f.
(microfarad) condensers, in parallel, and then attach them to a 110 volt a.-c. line so that an incandescent lamp is in circuit as shown in Fig.
437. The lamp will be found to glow brightly, although there is no electrical connection between the two sets of condenser plates. If the same arrangement is connected to a 110 volt direct current circuit, the lamp does not glow because it is really an open circuit. The lamp glows on an a.-c. circuit because, although no electricity flows _through_ the condenser, it does flow _into and out of_ the condenser, surging back and forth through the lamp with sufficient intensity to cause it to glow brightly. When the a.-c. current moves one way in the circuit, one set of plates of the condensers becomes charged positively, the other, negatively. When the a.-c. current reverses, the charges on the condenser plates reverse. In the ordinary lighting circuit 120 reversals take place each second, so that electricity rapidly flows into and out of the condensers. On removing one condenser after another from the circuit, the lamp is found to glow less and less, till when but one condenser is left, no glowing is observed, since one small condenser does not have sufficient _capacity_.
[Ill.u.s.tration: FIG. 437.--Twelve condensers in circuit with an incandescent lamp.]
The unit of capacity is the _Farad_. Capacity is defined as the quant.i.ty of electricity per second that flows into a condenser when the voltage at the terminals changes at the rate of one volt per second. If a change of one volt per second causes one coulomb to flow per second, that is, a current of one ampere, the capacity is one _farad_. The condensers used in the above experiment have a capacity of one microfarad, or one millionth of a farad.
A condenser, on account of its capacity, causes an a.-c. current to _lead_ the voltage, that is the current reaches its maximum value before the voltage does. In this respect a condenser has an effect opposite to that of the self-induction of a choke coil (the latter causing the current to "lag"). (See Fig. 435.)
=437. Transmission of Electric Power.=--A field of peculiar usefulness for a.-c. currents is in the economical transmission of electric power.
This fact is due to the following reasons: (_a_) The loss of electrical power in a transmission line is due to the production of heat; the heat produced being proportional to _IR_, or to the _square_ of the _current intensity_. Any lessening of the current flow required to transmit a given power will therefore increase the efficiency of transmission.
(_b_) In order to employ a small current in transmitting a large amount of power, we must use a very high e.m.f. Such high electromotive forces, say from 60,000 to 100,000 volts, can be obtained only by the use of a.-c. transformers, since it is not practicable to build a direct current generator capable of producing 60,000 volts. In large power transmission systems, a.-c. generators are used to produce powerful alternating currents. The e.m.f. is then stepped up to a suitable voltage (2300-100,000) by transformers and sent over transmission lines to the various places where the power is to be used; at these places suitable transformers "step-down" the e.m.f. to a convenient or safe voltage for use. (See Fig. 442 of a transmission line and Fig. 438 of a large power transmission system, and Fig. 439 of an a.-c. generator and power plant.)
[Ill.u.s.tration: FIG. 438.--Diagram of an alternating current high tension power system. (_A_) Alternator, (_Tu_) water turbine, direct connected to alternator, (_E_) exciter, (_T_{1}_) step-up transformers in power station, (_T_{2}_) step-down transformers in substation, (_M_) motor, (_L_) lamps, single-phase, three-wire system, (_T_{3}_) step-down transformers delivering three-phase current to rotary converter (_R_) which delivers direct current to the trolley line.]
=438. Power Factor.=--The _power factor_ is a matter of interest and importance in the use of a.-c. machines. Its meaning and use may be learned from the following explanation: In a direct current circuit, watts equals volts times amperes. In an alternating current circuit, this equation is true only when the current is "in step" with the voltage, that is, only when there is no _inductance_ or _capacity_ in the circuit. If current and voltage are out of step, _i.e._, if there is _lag_ or _lead_ (see Fig. 434), the product of volts and amperes gives only the _apparent power_, the ratio between true and apparent power depending on the amount of lag or lead. This ratio is called the power factor. In an a.-c. circuit, then, the power equation is: watts = volts amperes power factor, or power factor = true power/apparent power.
The product of volts and amperes is the _apparent power_ and is called volt-amperes in distinction from the true power or watts. Therefore the following is true: power factor = true watts/volt-amperes.
[Ill.u.s.tration: FIG. 439.--Power house showing alternators, direct connected to horizontal hydraulic turbines. Note the direct current "exciter" on end of shaft of alternator. (_Courtesy of General Electric Co._)]
=439. Single-phase Currents.=--There are several kinds of a.-c.
currents. One of the most common is the _single-phase_. It is simply the common a.-c. current used for light and power in the average home, and uses a two-wire circuit around which the current is rapidly alternating.
Fig. 440 ill.u.s.trates the changes of e.m.f. in an a.-c. single-phase current. It may be produced by a single coil rotating in a magnetic field. The curve of Fig. 440 represents one _cycle_, that is, one complete series of changes in the electromotive forces. At the end of the cycle the armature is in the same condition as at the beginning so far as the magnetic field is concerned. It then begins a new cycle. The ordinary commercial alternating current has a frequency of 60, that is 60 cycles per second. One rotation produces as many cycles as there are pairs of poles. For example, if there are 48 poles in the generator field, one rotation produces 24 cycles.
[Ill.u.s.tration: FIG. 440.--Graph showing the e.m.f. changes of a single-phase current for one "cycle."]
=440. Three-phase Currents.=--Now suppose we have three coils as in Fig.
441, the coils being evenly s.p.a.ced, or 120 degrees apart, at _A_, _B_, and _C_. If the coils are rotated in a magnetic field, each will produce an electromotive force. The result produced by three such coils is called a _three-phase_ current. Ordinarily six wires, or three circuits, would be required to carry the current produced by three separate coils; for when coil "_C_" is in the 90 degree position, where its e.m.f. is a maximum, coil "_B_" is 120 degrees past its maximum, and coil "_A_" is 240 degrees past its maximum. The graph (Fig. 441) shows the maximum points of the three e.m.f's. separated by intervals of 120 degrees. In practice, however, it is found possible to use _three wires_ instead of six, as explained in Art. 441.
[Ill.u.s.tration: FIG. 441.--Graph showing the e.m.f. changes of a three-phase current for one "cycle."]
=441. Three-wire Transmission.=--The currents produced in the three coils just described undergo precisely the same changes as those represented in the _graph_ (Fig. 441) for the three electromotive forces. Careful examination of the graph will show that at any point the sum of the _plus_ e.m.f's. equals the sum of the _minus_ e.m.f's. In other words the algebraic sum of the three e.m.f's. is zero. Therefore if we properly connect a transmission line of three wires to the generator, the sum of the currents leaving the generator will equal the sum of the currents returning to it. Since the algebraic sum of the currents produced by the three coil combination described in Art. 440 is always zero, it is possible to use three wires on three-phase transmission lines. Fig. 442 shows a "tower" carrying three, three-wire transmission lines. Long distance, high tension transmission lines are generally three-wire lines carrying three-phase a.-c. currents.
[Ill.u.s.tration: FIG. 442.--A "tower" supporting three, three-phase circuits of a high tension transmission line.]
=442. Alternators.=--A dynamo which delivers alternating current is known as an _alternator_. Commercial alternators have many pairs of poles in the field and as a rule the field rotates while the armature is stationary. The field must be supplied with _direct_ current for the polarity of each coil in the field must remain unchanged. Usually a separate "exciter" is used, which is a small direct current generator.
The current from this exciter is fed into the rotating field by means of slip rings. Fig. 439 shows a d.-c. (direct current) exciter on the end of the armature shaft of the large alternator.
[Ill.u.s.tration: FIG. 443.--Diagram of a "Series Motor."]
=443. The A.-C. Series Motors.=--The only type of motor that will run on either alternating or direct current is the _series motor_. The "universal" motor used in household appliances such as electric fans, vacuum cleaners, etc., is a series motor. The reason a series motor will run on either direct or alternating current is because the direction of rotation of the armature of a motor depends on (_a_) the direction of the current in the armature, and (_b_) the polarity of the field.
Reversing either of these alone, reverses the direction of rotation of the armature, while reversing both at the same instant leaves the direction of rotation unchanged. Fig. 443 is a diagram of a series motor since the field coils and armature are connected in series. On an a.-c.
line, both field and armature current must therefore reverse at the same instant. In a shunt motor (similar to Fig. 286) we have a divided circuit, and the greater self-induction of the field coils causes an a.-c. current through these coils to lag behind that flowing in the armature so that the two currents do not reverse at the same instant.
[Ill.u.s.tration: FIG. 444.--Diagram of a gramme ring. It is shown connected to a single-phase current so as to produce a rotating magnetic field, similar to that obtained with a three-phase current. (_Ahrens, Harley and Burns._)]
Physics Part 67
You're reading novel Physics Part 67 online at LightNovelFree.com. You can use the follow function to bookmark your favorite novel ( Only for registered users ). If you find any errors ( broken links, can't load photos, etc.. ), Please let us know so we can fix it as soon as possible. And when you start a conversation or debate about a certain topic with other people, please do not offend them just because you don't like their opinions.
Physics Part 67 summary
You're reading Physics Part 67. This novel has been translated by Updating. Author: Cope, Smith, Tower, and Turton already has 710 views.
It's great if you read and follow any novel on our website. We promise you that we'll bring you the latest, hottest novel everyday and FREE.
LightNovelFree.com is a most smartest website for reading novel online, it can automatic resize images to fit your pc screen, even on your mobile. Experience now by using your smartphone and access to LightNovelFree.com
- Related chapter:
- Physics Part 66
- Physics Part 68